语言
The distributed air-cooled system is a cooling method that uses air as the cooling medium and realizes heat exchange through dispersedly arranged heat dissipation units. It is widely used in fields such as electronic equipment, communication base stations, and industrial machinery.
Contact Us
| Product Model | HNES(F)-200KWH | HNES(F)-215KWH | HNES(F)-225KWH | HNES(F)-241KWH | HNES(F)-241KWH | HNES(F)-369KWH |
| Battery-side Parameters | ||||||
| Cell Type | 280AH(Lithium Iron Phosphate) | 280AH(Lithium Iron Phosphate) | 314AH(Lithium Iron Phosphate) | 314AH(Lithium Iron Phosphate) | 314AH(Lithium Iron Phosphate) | 314AH(Lithium Iron Phosphate) |
| System Battery Configuration | 1P224S | 1P240S | 1P224S | 1P240S | 1P352S | 1P368S |
| DC-side Battery Capacity | 200.704KWH | 215.04KWH | 225.075KWH | 241.152KWH | 353.689KWH | 369.766KWH |
| Battery Voltage Range | 627~817V | 672~876V | 627~817V | 672~876V | 1020~1284V | 1067~1343V |
| Charge and Discharge Rate | ≤0.5P | ≤0.5P | ≤0.5P | ≤0.5P | ≤0.5P | ≤0.5P |
| PCS Parameters | ||||||
| Rated Power | 100kw | 105kw | 112kw | 120kw | 176kw | 184kw |
| Rated Grid Voltage | 400VAC | 400VAC | 400VAC | 400VAC | 400VAC | 400VAC |
| Rated Current | 151A | 159A | 170A | 182A | 147A | 153A |
| Rated Grid Frequency | 50Hz/60Hz | 50Hz/60Hz | 50Hz/60Hz | 50Hz/60Hz | 50Hz/60Hz | 50Hz/60Hz |
| Total Harmonic Distortion of Curren | ≤2%(Rated power) | ≤2%(Rated power) | ≤2%(Rated power) | ≤2%(Rated power) | ≤2%(Rated power) | ≤2%(Rated power) |
| Power Factor | >0.99(Rated power) | >0.99(Rated power) | >0.99(Rated power) | >0.99(Rated power) | >0.99(Rated power) | >0.99(Rated power) |
| Power Factor Range | -1(Leading)-1(Lagging) | -1(Leading)-1(Lagging) | -1(Leading)-1(Lagging) | -1(Leading)-1(Lagging) | -1(Leading)-1(Lagging) | -1(Leading)-1(Lagging) |
| System Parameters | ||||||
| Cabinet Dimensions (W*D*H) | 1630*1150*2400 | 2240*1150*2400 | ||||
| Weight | 2500kg | 2650kg | 2500kg | 2650kg | 3000kg | 3150kg; |
| Ingress Protection (IP) Rating | IP54 | |||||
| Corrosion Resistance Rating | C3/C5 | |||||
| Operating Humidity Range | 0~95%(Non-condensing) | |||||
| Operating Temperature Range | -30~50℃(With derating above 45℃) | |||||
| Cooling Method | Intelligent Air Cooling | |||||
| Maximum Operating Altitude | 3000m(above sea level) | |||||
| Communication | Ethernet | |||||
| Communication Protocol Modbus TCP | Moudus TCP | |||||
| Compliance with Standards | GB/T 36547 GB/T 36548 | |||||